Models with large capacities ranging from 375 to 2500 USRT are available, which support a wide range of applications from use in large buildings to industrial use.

Product outline

  1. Uses low-pressure refrigerant HCFC-123 (RTCS series) or HFC-245fa (RTCF series)

    The chiller provides high cycle efficiency, contributing to the reduction of CO2 emissions.
    The chillier using low-pressure refrigerant is exempted from regulations imposed by the High Pressure Gas Safety Act. It can be shipped as separate modules for easy transportation and requires no qualified personnel for operation.

  2. Energy-saving series with a COP of 6.0 or more, while providing the highest performance in the industry

    With a 3-stage compression/2-stage economizer cycle and high-performance heat transfer tube, the chiller provides improved cycle efficiency.
    The unit has a compressor connected directly to a motor, minimizing mechanical loss (no gear loss). Equipped with an optional inverter, the unit also offers improved partial load characteristics.

  3. With improved maintainability

    Because of the adoption of ball bearings, the chiller operates with a smaller amount of lubricant and provides highly reliable operation.
    In addition, the chiller has a new intelligent control panel that improves the system reliability and facilitates operation control.

Standard Specifications for RTCS (50 Hz)

Model Cooling Capacity kW {USRT} Rated Motor Output kW
RTCS5L040 1407 {400} 220
RTCS5L050 1758 {500} 270
RTCS5L060 2110 {600} 315
RTCS5L070 2461 {700} 365
RTCS5L080 2813 {800} 425
Chilled water: 12/7 °C and cooling water: 32/37 °C.

Standard Specifications for RTCS (60 Hz)

Model Cooling Capacity kW {USRT} Rated Motor Output kW
RTCS6L040 1407 {400} 230
RTCS6L050 1758 {500} 275
RTCS6L060 2110 {600} 320
RTCS6L070 2461 {700} 370
RTCS6L080 2813 {800} 420
Chilled water: 12/7 °C and cooling water: 32/37 °C.

Standard Specifications for RTCF (50 Hz)

Model Cooling Capacity kW {USRT} Rated Motor Output kW
RTCF5L080 2813 {800} 425
RTCF5L090 3165 {900} 475
RTCF5L100 3515 {1000} 525
RTCF5L115 4044 {1150} 595
RTCF5L125 4395 {1250} 645
RTCF5L160D 5626 {1600} 425 × 2
RTCF5L180D 6330 {1800} 460 × 2
RTCF5L200D 7032 {2000} 510 × 2
RTCF5L230D 8088 {2300} 575 × 2
RTCF5L250D 8790 {2500} 620 × 2
Chilled water: 12/7 °C and cooling water: 32/37 °C.

Standard Specifications for RTCF (60 Hz)

Model Cooling Capacity kW {USRT} Rated Motor Output kW
RTCF6L080 2813 {800} 425
RTCF6L090 3165 {900} 480
RTCF6L100 3515 {1000} 525
RTCF6L115 4044 {1150} 600
RTCF6L125 4395 {1250} 655
RTCF6L160D 5626 {1600} 425 × 2
RTCF6L180D 6330 {1800} 470 × 2
RTCF6L200D 7032 {2000} 515 × 2
RTCF6L230D 8088 {2300} 580 × 2
RTCF6L250D 8790 {2500} 630 × 2
Chilled water: 12/7 °C and cooling water: 32/37 °C.

Refrigerant Properties

Refrigerant HFC-245Fa HCFC-123 HFC-134a
Molecular Formula CO3CH2CHF2 C2HC2F3 C2H2F4
ODP 0 0.012 0
GWP 950 120 1300
Atmospheric Lifetime (Estimated Years) 7.2 1.4 13.8
Condensing Pressure (kPa, 43 °C) 281 172 1111
Suction Flow Rate (*1) 0.102 0.158 0.026
Theoretical COP (*2) 7.62 7.68 7.43
*1) m3/(min-kW), steam temperature: 4.4 °C, condensing temperature: 43 °C, degree of superheat: 1.1 °C.
*2) Values in the case of 3-stage compression under the same conditions as listed above and with a degree of supercooling of 0 °C and a compression efficiency of 80 %.