RTBF SERIES HIGH-EFFICIENCY CENTRIFUGAL CHILLER (USING LOW-PRESSURE REFRIGERANT (HFC-245fa))

Six standard high-efficiency models with a cooling capacity of 220 to 1500 USRT are available.

Product outline

  1. Lineup of high-efficiency models, all with a COP of 6.0 or more

    With a high-performance compressor, this chiller is highly cost-efficient and very compact. It contributes to the reduction of CO2 emissions.

  2. Uses low-pressure refrigerant HFC-245fa

    The chiller provides high cycle efficiency, contributing to the reduction of CO2 emissions.
    Safe, environmentally-friendly standard models using low-pressure refrigerant are available.

Standard Specifications (Representative Examples)

Model RTBF030 RTBF050 RTBF075
Cooling Capacity kW 1,055 1,758 2,637
{USRT} 300 500 750
Rated Motor Output kW 160 260 385
Main Power Supply 50/60 Hz 400V/3 kV/6 kV Class 400V/3 kV/6 kV Class 400V/3kV/6kVClass
Chilled Water Inlet/Outlet Temp. °C 12/7 (14/7) 12/7 (14/7) 12/7(14/7)
Flow Rate l/min 3,020 (2,160) 5,040 (3,600) 7,560(5,400)
Pressure Drop kPa 56 (82) 53 (77) 55(96)
Pipe Connection Dia. A 150 200 300
Number of Passes - 2 2 2
Cooling Water Inlet/Outlet Temp. °C 32/37 32/37 32/37
Flow Rate l/min 3,550 (3,540) 5,890 (5,880) 8,840(8,830)
Pressure Drop kPa 55 55 55
Pipe Connection Dia. A 200 250 300
Number of Passes - 2 2 2
Outer Dimensions Length (L) mm 4,380 (4,550) 4,500 (4,550) 4,865(4,550)
Width (W) mm 1,970 2,450 2,930
Height (H) mm 1,930 2,380 2,765
Weight Product Weight t 6.2 10 13.3
Operating Weight t 7.4 12 16