REW /RGWA SERIES DOUBLE EFFECT TYPE

This chiller achieves excellent energy efficiency over the entire operating range, from the rated load to prolonged partial load, with an inverter-controlled solution pump.

Product outline

  1. Shorter start-up time

    This chiller optimizes the circulating amount of solution at the time of start-up to reduce the start-up time.

  2. Minimizes the dilution time during the stop process

    The chiller judges the operation status at the time of stop to determine the optimum dilution time.
    The chiller can prevent extra dilution operation that reduces the energy-saving effect.

  3. Equipped with an auxiliary equipment interlocking circuit as standard

    The chiller is equipped with an interlocking circuit for the chilled water/cooling water pump and cooling tower fan as standard.
    Equipped with a start-stop circuit for the cooling tower fan as standard, including a thermosensor, the chiller helps to reduce the cost of equipment.

  4. Digitally displays the operation status

    The chiller has a control panel that can digitally display data required for operation control, such as the chilled water temperature, cooling water temperature, solution temperature, and operating time, on an individual basis.

Representative Specifications (Steam Consumption Rate: 3.9 kg/(h・USRT))

Model Cooling Capacity Steam Consumption Dimensions (mm) Operating Weight
kW {USRT} kg/h Length Depth Height t
REW015 528 {150} 585 3580 1680 1900 7.4
REW036 1266 {360} 1404 4665 2075 2250 15.1
REW050 1759 {500} 1950 4810 2285 2550 19.2
RAW080 2813 {800} 3600 6930 2370 3000 28
RAW100 3517 {1000} 4500 6940 2600 3360 36
RAW150 5275 {1500} 6750 7130 3210 4155 52
  • Distributer Network